AH/AU-A079E
AH/AU-A099E
13.Test mode13-2 TEST 2 (For output of each operation checking)
13-1 TEST 1 (For control circuit operation checking)Keep pushing both the buttons, "AUX." and "TEST
Make terminals 1 and 2 of connector CN4 short-RUN", and supply the power, the system will go to
circuited and supply the power.the test 2 mode.
Hereby the timer's period becomes shortened. InIn this mode, the output of operation is switched by
this test mode, the control times are shortend aspushing the "TEST RUN" button in the unit or the
follows."OI" button in the remote controller.
Use the "AUX." button to back to step 1.
The operation LED flicker's period:Normal outputs are shown in Table H-5 and H-6.
in Test run : not
The protector timer:shortened
The defrost timer:
Other controls: 1/60 (ex.; 3 min. to 3 sec.)
Table H-5 [AH-A079E]
LampsIndoor
Louver
Step Output for outdoor unit
Fan motor
REDYELLOW
1OFF 12 OFF OPEN
2ON FlickeringON DOFF
3OFF ON OFF M OFF
4OFF ON ON L CLOSE
5OFF ONOFF D OFF
6OFF OFFOFF ULOFF
7OFF OFFOFF 3H OFF
8OFF OFF OFFMOFF
9OFF ON ON L OFF
10OFF OFF ON OFF OFF
11OFF ON OFF OFF OFF
12OFF ONOFFOFF OFF
13OFF OFF OFF OFF OFF
14OFF ON ON OFF OFF
15OFF ONON OFF OFF
16OFF ON OFF OFF OFF
17OFF OFF OFF OFF OFF
18OFF OFFOFF OFF OFF
19OFF OFF OFF OFF OFF
20OFF ON OFF OFF OFF
21OFF OFFOFF OFF OFF
22OFF OFF OFF OFF OFF
23OFF OFF OFF OFF OFF
(Back to step 1)
1: 7uC Room temp. 42uC ON
: 7uC (Room temp.) or (Room temp.) 42uC OFF
2: �2uC Pipe temp. 42uC ON
: �2uC (Pipe temp.) or (Pipe temp.) 42uC OFF
3: ON in the case of Power on start.
12 |