Ventilation
The room containing the cooker should
have an air supply in accordance with B.S.
5440: Part 2: Current Editions.
The following requirements for ventilation
must be met.
The cooker should not be installed in a bed
sitting room with a volume of less than
3
20m, if it is installed in a room of volume
3
less 5m an air vent of effective area of
2
110cm is required; if it is installed in a room
33
of volume between 5m and 10m, an air
2
vent of effective area 50cm is required,
3
while if the volume exceeds 11mno air vent
is required. However, if the room has a
door, which opens directly to the outside, no
air vent is required even when the volume is
33
between 5m and 11m.
If there are other fuel burning appliances in
the same room, B.S. 5440: Part. 2: Current
Editions should be consulted to determine
the requisite air vent requirements.
Location
The cooker may be located in a kitchen, a
kitchen/diner or bed sitting room but not in a
bathroom or shower room.
For information regarding the fitting of
flexible supply pipes, the highest
temperature at the rear of this cooker which
may come into contact with the supply pipe
is 70°C above ambient.
When the appliance has been installed
there must be enough space for the hotplate
lid (when present) to open fully.
L.P.G. cookers or ovens MUST NOT
be installed below ground level, i.e. in a
basement, or aboard any boat, yacht or
other vessel.
Levelling
Fix the support with two legs by means of
washer and nuts, delivered with the
cooker, see the figure.
19 |