Attached accessories
Piping length and the elevation
Pipe size Max.Max.RatedAdditional
Model Gas LiquidPipingElevationLengthElevationRefrigerant
LengthB (m)(g/m)
A (m)
C28BKP55/8?1/4?30257.5540
Example:
If the unit will be installed at a 12 m distance, the quantity of
additional refrigerant should be 80 g...(12-10 m) � 40 g/m = 80g
Indoor/Outdoor unit installation diagram
Applicable: Flaring piping kit CZ-52F
SELECT THE BEST LOCATION
INDOOR UNIT
? There should not be any heat source or steam near the
unit.
? There should not be any obstacles blocking the air
circulation.
? A place where air circulation in the room is good.
? A place where air drainage can be easily done.
? A place where noise prevention is taken into
consideration.
? Do not install the unit near the door way.
? Ensure the spaces indicated by arrows from the wall,
ceiling, or other obstacles.
? Indoor unit of this room air conditioner shall be installed
on the wall in a height of at least 2.5 m.
OUTDOOR UNIT
? If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
? There should not be any animal or plant which could be
affected by hot discharged air.
? Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
? Do not place any obstacles which may cause a short
circuit of the discharged air.
? If piping length is over 10 m, additional refrigerant
should be added as shown in the table.
? This illustration is for explanation purposes only.
The indoor unit will actually face a different way. |