Operation Details
8) Airflow Direction Control
Airflow Direction Auto-Control
Horizontal
Upper limit
? When set a Airflow Direction Auto-Control with
remote control, the louver swings up and down as34!
shown in the diagram.
? The louver does not swing when the Indoor Fan
stops during operation.Swing up and down
? When stopped with remote control, the discharge46!
Lower limit for
vent is closed with the louver.
Cooling Mode and
Soft Dry Mode
Lower limit for Heating Mode
* The left and right airflow direction louvers can be
adjusted manually.
* 1 There is no swinging while indoor fan is stopped during Cooling and Soft Dry operation.
* 2 In Heating operation, when the indoor heat exchanger temperature rises to 38!C, the airflow direction is changed
from upper limit to lower limit. When the indoor heat exchanger temperature falls to 35!C, the air flow direction
is changed from lower limit to upper limit.
Airflow Direction Manual Control
? When the airflow direction set button is pressed,
the automatic airflow is released and the airflow
direction louver move up and down in the rangeHorizontal
Upper limit
shown in the diagram.
The louver can be stopped by releasing the button34!
at the desired louver position.
? When the remote control is used to stop the opera-
tion, the discharge vent is closed with airflow
57!
direction louver.
Lower limit for
Cooling Mode and
Soft Dry Mode
Lower limit for Heating Mode
The louver can be adjusted with in a range
OAirflow Direction Setting Button� is pressed.
* The left and right airflow direction louvers can be
adjusted manually.
9) Delay ON Timer Control
Y When the Delayed ON Timer is set by using the remote control, the unit will start operate slightly before the set time,
so that the room will reach nearly to the set temperature by the desired time.
Y For Cooling and Soft Dry mode, the operation will start, 15 minutes before the set time.
Y For Heating mode, the operation will start 30 minutes before the set time.
Y For Automatic mode, the indoor fan will operate at SLo speed for 20 seconds, 30 minutes before the set time to detect
the intake air temperature to determine the operation mode. The operation indication lamp will blink at this time.