14-2 TEST 2 (For output of each operation checking)
Test mode is for checking output of each operation. Keep pushing both the buttons, "AUX." and "TEST RUN",
and supply the power, the system will go to the test 2 mode.
In this mode, the output of operation is switched by the "TEST RUN" button in the unit or the "OI" button in the
remote controller. Use the "AUX." button to back to step 1. Normal outputs are shown in Table H-5.
Table Y-5
LampsIndoor
Louver
Step Output for outdoor unit
REDYELLOWFan motor
1 OFF 12 OFF OPEN
2 ON FlickeringON DOFF
3 OFF ON OFF M OFF
4 OFF ON ON L CLOSE
5 OFF ON ON D OFF
6 OFF ON 3ULOFF
7 OFF OFF ON 4H OFF
8 OFF ON OFF MOFF
9 OFF ON ON L OFF
10 OFF ON 5OFF 6OFF OFF
11 OFF ON OFF OFF OFF
12 OFF OFF ON OFF OFF
13 OFF OFF OFF OFF OFF
14 OFF ON ON OFF OFF
15 OFF ON OFF OFF OFF
16 OFF OFF OFF OFF OFF
17 OFF ON ON OFF OFF
18 OFF OFF OFF OFF OFF
19 OFF ON OFF OFF OFF
20 OFF ON ON OFF OFF
21 OFF ON ON OFF OFF
22 OFF OFFOFF OFF OFF
(Back to step 1)
1: 7uC Room temp. 42uC ON
: 7uC (Room temp.) or (Room temp.) 42uC OFF
2: �2uC Pipe temp. 42uC ON
: �2uC (Pipe temp.) or (Pipe temp.) 42uC OFF
3: 0.1V (ANI2 INPUT VOLTAGE) 0.45V ON
: 0.1V (ANI2 INPUT VOLTAGE) or (ANI2 INPUT VOLTAGE) 0.45V OFF
4
: OFF in the case of Power on start
5
: OFF in the case of Auto restart
6: ON in the case of Auto restart
12 |