CS-A181KR
Functions
Outdoor Unit
4-Way Valve Control2-Way Valve Control
Y When the unit is switched to "OFF" duringY 2-way valve is ON for 1 minutes after
Heating operation, 4-way valve stays atcompressor start. Other than this, 2-way
Heating Position for 5 minutes.valve is OFF. (A241K only)
Overload Protector
Y Inner protector (Compressor, Fan Motor).
60 Secs. Forced Operation Control
Y Once the compressor is activated, it does
not stop for 60 secs. (Stops immediately
with remote control stop signal.)
Outdoor Fan Operation Control
Y 4-pole induction motor (2-speed)
Y For Cooling or Soft Dry Operation
Hi-speed � when outdoor temperature
reaches to 31!C
Lo-speed � when outdoor temperature
reaches to 29!C
Y For Heating Operation
Hi-speed ... when outdoor temperature
reaches to 13.5!C.
Lo-speed ... when outdoor temperature
reaches to 15.5!C.
Y For Over-heating Protection, the Fan is
switched ON or OFF depending on the
piping temperature and the outdoor tem-
perature.
Deice Control
Y To prevent frosting at outdoor heat
exchanger during Heating Operation.