8.7.Airflow Direction Control
Airflow Direction Auto-ControlAirflow Direction Manual Control
? When set a Airflow Direction Auto-Control with remote? When the airflow direction set button is pressed, the
control, the louver swings up and down as shown in theautomatic airflow is released and the airflow direction louver
diagram.move up and down in the range shown in the diagram.
? The louver does not swing when the Indoor Fan stopsThe louver can be stopped by releasing the button at the
during operation.desired louver position.
? When stopped with remote control, the discharge vent ? Whenisthe remote control is used to stop the operation, the
closed with the louver.discharge vent is closed with airflow direction louver.
The left and right airflow direction louvers can be adjusted
manually.
1 There is no swinging while indoor fan is stopped during
Cooling and Soft Dry operation.
The left and right airflow direction louvers can be adjusted
manually.
8.8.Delay ON Timer Control
? When the Delayed ON Timer is set by using the remote,controlthe unit will start operate slightly before the set time, so that
the room will reach nearly to the set temperature by the desired time.
? For Cooling and Soft Dry mode, the operation will start 15 minutes before the set time.
? For Automatic mode, the indoor fan will operate at SLo speed for 20 seconds, 15 minutes before the set time to detect the
intake air temperature to determine the operation mode. The operation indication lamp will blink at this time. |