8.1. Cooling Mode Operation
Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
? When the compressor is stopped by Power Switch, Remote Control or there is a power failure, it restarts after 3 minutes when
the Power Switch, Remote Control is turned ON or the power supply is resumed.
? When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
7 minutes TimeSaved Control
? The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is below the compressor
ON temperature.
Anti-Freezing Control
? If the temperature of the indoor heat exchanger falls
continuously below 1°C forminute4 s, the compressor turns
off to protect the indoor heat exchanger from freezing. The
fan speed setting remains the same.
? Compressor recommences when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is
valid for Cooling Operation. |